General information
|
|
|
|
|
Product type designation
|
DQ 4x24VDC/2A ST
|
DQ 8x24VDC/0.5A ST
|
DQ 16x24VDC/0.5A ST
|
|
Product function
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
|
Engineering with
|
|
|
|
|
|
V11 SP2 with HSP0024 / -
|
V11 SP2 with HSP0024 / -
|
V11 SP2 with HSP0024 / -
|
|
|
V5.5 SP2 with GSD file / -
|
V5.5 SP2 with GSD file / -
|
V5.5 SP2 with GSD file / -
|
|
Supply voltage
|
|
|
|
|
Type of supply voltage
|
DC
|
DC
|
DC
|
|
Rated value (DC)
|
24 V
|
24 V
|
24 V
|
|
Reverse polarity protection
|
Yes
|
Yes
|
Yes
|
|
Digital outputs
|
|
|
|
|
Number of digital outputs
|
4; > 60 ?C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A
|
8; > 60 ?C max. total current 1.0 A
|
16; > 60 ?C max. total current 1.0 A
|
|
Short-circuit protection
|
Yes
|
Yes
|
Yes
|
|
Limitation of inductive shutdown voltage to
|
Typ. L (-50 V)
|
Typ. L (-50 V)
|
Typ. L (-50 V)
|
|
Controlling a digital input
|
Yes
|
Yes
|
Yes
|
|
Switching capacity of the outputs
|
|
|
|
|
|
2 A
|
0.5 A
|
0.5 A
|
|
|
10 W
|
5 W
|
5 W
|
|
Load resistance range
|
|
|
|
|
|
12 ?
|
48 ?
|
48 ?
|
|
|
3 400 ?
|
12 k?
|
12 k?
|
|
Output current
|
|
|
|
|
|
2 A
|
0.5 A
|
0.5 A
|
|
|
0.1 mA
|
0.1 mA
|
0.1 mA
|
|
Output delay with resistive load
|
|
|
|
|
|
50 ?s
|
50 ?s
|
50 ?s
|
|
|
100 ?s
|
100 ?s
|
100 ?s
|
|
Parallel switching of two outputs
|
|
|
|
|
|
No
|
No
|
No
|
|
|
Yes
|
Yes
|
Yes
|
|
Switching frequency
|
|
|
|
|
|
100 Hz
|
100 Hz
|
100 Hz
|
|
|
2 Hz
|
2 Hz
|
2 Hz
|
|
|
10 Hz
|
10 Hz
|
10 Hz
|
|
Total current of the outputs
|
|
|
|
|
|
8 A
|
4 A
|
8 A
|
|
Cable length
|
|
|
|
|
|
1 000 m
|
1 000 m
|
1 000 m
|
|
|
200 m
|
200 m
|
200 m
|
|
Isochronous mode
|
|
|
|
|
Isochronous operation (application synchronized up to terminal)
|
Yes
|
Yes
|
Yes
|
|
Interrupts/diagnostics/status information
|
|
|
|
|
Substitute values connectable
|
Yes
|
Yes
|
Yes
|
|
Alarms
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
|
Diagnostic messages
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
|
|
Yes
|
Yes
|
Yes
|
|
|
Yes
|
Yes
|
Yes
|
|
Diagnostics indication LED
|
|
|
|
|
|
Yes; green PWR LED
|
Yes; green PWR LED
|
Yes; green PWR LED
|
|
|
Yes; Green LED
|
Yes; Green LED
|
Yes; Green LED
|
|
|
Yes; green/red DIAG LED
|
Yes; green/red DIAG LED
|
Yes; green/red DIAG LED
|
|
Potential separation
|
|
|
|
|
Potential separation channels
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
|
Isolation
|
|
|
|
|
Isolation tested with
|
707 V DC
|
707 V DC
|
707 V DC
|
|
Highest safety class achievable in safety mode
|
|
|
|
|
|
d
|
d
|
d
|
|
|
2
|
2
|
2
|
|
Ambient conditions
|
|
|
|
|
Ambient temperature during operation
|
|
|
|
|
|
-40 ?C; = Tmin
|
-40 ?C; = Tmin
|
-40 ?C; = Tmin
|
|
|
70 ?C; = Tmax; > 60 ?C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A
|
70 ?C; = Tmax; > 60 ?C max. total current 1.0 A
|
70 ?C; = Tmax; > 60 ?C max. total current 1.0 A
|
|
|
-40 ?C; = Tmin
|
-40 ?C; = Tmin
|
-40 ?C; = Tmin
|
|
|
50 ?C; = Tmax
|
50 ?C; = Tmax
|
50 ?C; = Tmax
|
|
Extended ambient conditions
|
|
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... 2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa ( 2000 m ... 3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa ( 3500 m ... 5000 m)
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... 2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa ( 2000 m ... 3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa ( 3500 m ... 5000 m)
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... 2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa ( 2000 m ... 3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa ( 3500 m ... 5000 m)
|
|
Relative humidity
|
|
|
|
|
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
|
Resistance
|
|
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
|
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
|
Dimensions
|
|
|
|
|
Width
|
15 mm
|
15 mm
|
15 mm
|
|
Weights
|
|
|
|
|
Weight, approx.
|
30 g
|
28 g
|
28 g
|