General information
|
|
|
Vendor identification (VendorID)
|
801Eh
|
|
Supply voltage
|
|
|
Rated value (DC)
|
|
|
|
Yes
|
|
permissible range (ripple included), lower limit (DC)
|
20.4 V
|
|
permissible range (ripple included), upper limit (DC)
|
28.8 V
|
|
external protection for power supply lines (recommendation)
|
2,5 A
|
|
Mains buffering
|
|
|
|
5 ms
|
|
Input current
|
|
|
Current consumption, max.
|
650 mA; with 24 V DC supply
|
|
Inrush current, typ.
|
3 A
|
|
I?t
|
0.1 A??s
|
|
Output current
|
|
|
for backplane bus (5 V DC), max.
|
1.5 A
|
|
Power loss
|
|
|
Power loss, typ.
|
5.5 W
|
|
Address area
|
|
|
Addressing volume
|
|
|
|
244 byte
|
|
|
244 byte
|
|
Hardware configuration
|
|
|
Number of modules per DP slave interface, max.
|
12
|
|
Time stamping
|
|
|
Accuracy
|
1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules
|
|
Number of message buffers
|
|
|
Messages per message buffer
|
20
|
|
Number of stampable digital inputs, max.
|
128; Max. 128 signals/station; max. 32 signals/slot
|
|
Time format
|
RFC 1119
|
|
Time resolution
|
0.466 ns
|
|
Time interval for transmitting the message buffer if a message is present
|
1 000 ms
|
|
Time stamp on signal change
|
rising / falling edge as signal entering or exiting
|
|
Interfaces
|
|
|
Interface physics, RS 485
|
Yes
|
|
Interface physics, FOC
|
No
|
|
PROFIBUS DP
|
|
|
|
1 to 125 permitted
|
|
|
Yes
|
|
|
70 mA
|
|
|
12 Mbit/s
|
|
|
RS 485
|
|
|
Yes
|
|
|
Yes
|
|
|
Yes; as publisher with all IO, as subscriber with F-IO only
|
|
|
9-pin sub D
|
|
1. Interface
|
|
|
DP slave
|
|
|
|
SI05801E.GSG
|
|
|
Yes
|
|
Protocols
|
|
|
Bus protocol/transmission protocol
|
PROFIBUS DP to EN 50170
|
|
Isolation
|
|
|
Isolation tested with
|
Isolation voltage 500 V
|
|
Degree and class of protection
|
|
|
Degree of protection acc. to EN 60529
|
|
|
|
Yes
|
|
Standards, approvals, certificates
|
|
|
CE mark
|
Yes
|
|
Ambient conditions
|
|
|
Ambient temperature during operation
|
|
|
|
-40 ?C; = Tmin; Startup @ -25 ?C
|
|
|
70 ?C; = Tmax
|
|
Ambient temperature during storage/transportation
|
|
|
|
-40 ?C
|
|
|
70 ?C
|
|
Extended ambient conditions
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... 2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa ( 2000 m ... 3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa ( 3500 m ... 5000 m)
|
|
|
-25 ?C
|
|
Relative humidity
|
|
|
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
|
Resistance
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
|
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
|
Configuration
|
|
|
Configuration software
|
|
|
|
Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
|
|
Dimensions
|
|
|
Width
|
40 mm
|
|
Height
|
125 mm
|
|
Depth
|
117 mm
|
|
Weights
|
|
|
Weight, approx.
|
360 g
|