Supply voltage
|
|
|
|
|
|
Load voltage L
|
|
|
|
|
|
|
24 V
|
24 V
|
24 V
|
24 V
|
|
Input current
|
|
|
|
|
|
from load voltage L (without load), max.
|
60 mA
|
90 mA
|
80 mA
|
160 mA
|
|
from backplane bus 5 V DC, max.
|
40 mA
|
70 mA
|
80 mA
|
110 mA
|
|
Power loss
|
|
|
|
|
|
Power loss, typ.
|
6.8 W
|
5 W
|
4.9 W
|
6.6 W
|
|
Digital outputs
|
|
|
|
|
|
Number of digital outputs
|
8
|
8
|
|
32
|
|
Limitation of inductive shutdown voltage to
|
L (-48 V)
|
L (-45 V)
|
L (-53 V)
|
L (-53 V)
|
|
Switching capacity of the outputs
|
|
|
|
|
|
|
10 W
|
5 W
|
5 W
|
5 W
|
|
Load resistance range
|
|
|
|
|
|
|
12 ?
|
48 ?
|
48 ?
|
48 ?
|
|
|
4 k?
|
3 k?
|
4 k?
|
4 k?
|
|
Output voltage
|
|
|
|
|
|
|
L (-0.8 V)
|
L (-0.8 to -1.6 V)
|
L (-0.8 V)
|
L (-0.8 V)
|
|
Output current
|
|
|
|
|
|
|
2 A
|
0.5 A
|
0.5 A
|
0.5 A
|
|
|
5 mA
|
10 mA
|
5 mA
|
5 mA
|
|
|
2.4 A
|
0.6 A
|
0.6 A
|
0.6 A
|
|
|
5 mA
|
10 mA
|
5 mA
|
5 mA
|
|
|
2.4 A
|
0.6 A
|
0.6 A
|
0.6 A
|
|
|
5 mA
|
10 mA
|
5 mA
|
5 mA
|
|
|
0.5 mA
|
0.5 mA
|
0.5 mA
|
0.5 mA
|
|
Switching frequency
|
|
|
|
|
|
|
100 Hz
|
100 Hz
|
100 Hz
|
100 Hz
|
|
|
0.5 Hz
|
2 Hz
|
0.5 Hz
|
|
|
|
10 Hz
|
10 Hz
|
10 Hz
|
10 Hz
|
|
Total current of the outputs (per group)
|
|
|
|
|
|
horizontal installation
|
|
|
|
|
|
|
|
4 A
|
4 A
|
4 A
|
|
|
4 A
|
3 A
|
3 A
|
3 A
|
|
|
4 A
|
2.5 A; (without diode) & 1.5 A (with diode)
|
3 A
|
2 A
|
|
vertical installation
|
|
|
|
|
|
|
4 A
|
4 A
|
2 A
|
2 A
|
|
Cable length
|
|
|
|
|
|
|
1 000 m
|
1 000 m
|
1 000 m
|
1 000 m
|
|
|
600 m
|
600 m
|
600 m
|
600 m
|
|
Interrupts/diagnostics/status information
|
|
|
|
|
|
Diagnostic functions
|
No
|
Yes; Parameterizable
|
No
|
No
|
|
Alarms
|
|
|
|
|
|
|
No
|
Yes; Parameterizable
|
No
|
No
|
|
Potential separation
|
|
|
|
|
|
Potential separation digital outputs
|
|
|
|
|
|
|
Yes
|
|
Yes
|
Yes
|
|
|
4
|
8
|
8
|
8
|
|
|
Yes; Optocoupler
|
Yes; Optocoupler
|
Yes; Optocoupler
|
Yes; Optocoupler
|
|
Isolation
|
|
|
|
|
|
Isolation tested with
|
500 V DC
|
500 V DC
|
500 V DC
|
500 V DC
|
|
Standards, approvals, certificates
|
|
|
|
|
|
CE mark
|
Yes
|
Yes
|
Yes
|
Yes
|
|
UL approval
|
Yes; File E239877
|
Yes; File E239877
|
Yes; File E239877
|
Yes; File E239877
|
|
FM approval
|
Yes
|
Yes; CofC 3028431
|
Yes; CofC 3028431
|
Yes; CofC 3028431
|
|
RCM (formerly C-TICK)
|
|
Yes
|
Yes
|
Yes
|
|
KC approval
|
|
Yes
|
Yes
|
Yes
|
|
EAC (formerly Gost-R)
|
|
Yes
|
Yes
|
Yes
|
|
Railway application
|
|
|
|
|
|
|
No
|
|
|
|
|
|
No
|
Yes; T1 Category 1 Class A/B horizontal mounting position
|
Yes; T1 Category 1 Class A/B horizontal mounting position
|
Yes; T1 Category 1 Class A/B horizontal mounting position
|